Description
Electric Motors
Frame | 324TS |
---|---|
Output | 40 HP (30 kW) |
Number of Poles | 4 |
Frequency | 60 Hz |
Rated speed | 1775 rpm |
Slip | 1.39 % |
Rated voltage | 230/460 V |
Rated current | 96.4/48.2 A |
L. R. Amperes | 578/289 A |
LRC | 6.0x(Code G) |
No load current | 32.0/16.0 A |
Rated torque | 118 ft.lb |
Locked rotor torque | 180 % |
Breakdown torque | 210 % |
Locked rotor time | 36s (cold) 20s (hot) |
Moment of inertia (J) | 5.37 sq.ft.lb |
---|---|
Design | B |
Insulation Class | F |
Service factor | 1.15 |
Temperature rise | 80 K |
Duty Cycle | Cont.(S1) |
Starting Method | Direct On Line |
Ambient temperature | -20°C to +40°C |
Altitude | 1000 m.a.s.l. |
Degree of Protection | IP23 |
Enclosure | IC01 – ODP |
Mounting | F-1 |
Rotation¹ | Both (CW and CCW) |
Approx. weight³ | 435 lb |
(1) Looking the motor from the shaft end.; (3) Approximate weight, subject to be changed after manufacturing process.; (4) At 100% of full load.
Efficiency
50% | 75% | 100% |
---|---|---|
92.4 | 93.0 | 93.0 |
Power factor
50% | 75% | 100% |
---|---|---|
0.72 | 0.81 | 0.84 |
Features
Frame Material | Cast Iron |
---|---|
Impregnation Method | Dip and Bake Polyester |
Regreasing System | At Drive end and Non-drive end |
Main terminal box hole | NPT 2″ |
Terminal Block | Without |
Shaft Locking Device | Without |
Shaft Material | SAE 1040/45 Carbon Steel |
Painting | RAL 3002 203A (ISO 12944 – C2) |
Grounding Lugs | Single |
Fan Cover material | Without Fan Cover |
Tropicalized Painting | Without |
Fan material | Without fan |
Bearing cap | Yes- Bearing Cap |
Bolt Material | Carbon Steel |
Balancing Method | 1/2 Key |
Drip Cover | Without |
Overload protector (phenolic) | Without overload protector |
Connection Cables Quantity | 12 |
Reviews
There are no reviews yet.